POWERFLEX 2200
Technology: Radar level
2-wire 4…20 mA guided radar (TDR) level transmitter for safety- and non-safety-related liquid applications in nuclear power plants, range up to 40 m.
The POWERFLEX 2200 measures level, distance, volume, mass or dielectric constant in liquids using Time Domain Reflectometry. It covers a measuring range of 0.6…40 m, process temperatures of -50…+150°C and pressures of -1…100 barg. It is qualified to IEEE 323, IEEE 344 and RCC-E, conforms to ASME Section III and RCC-M, and offers seismic qualification up to 300 m/s². Four versions (compact, compact with sensor extension, remote field, remote with double sensor extension) allow the converter to be installed up to 450 m from the probe in high-radiation areas.
Specifications
- Measuring Range
- 0.6…40 m / 2…131 ft
- Process Temperature
- -50…+150°C / -58…+302°F
- Process Pressure
- -1…100 barg / -14.5…1450 psig
- Output Signal
- 2-wire 4…20 mA
- Measuring Principle
- Guided radar, Time Domain Reflectometry (TDR)
- Max. Converter Distance From Probe
- 450 m / 1476.38 ft
- Seismic Qualification
- Up to 300 m/s2
- Thermal Aging Qualification
- +107°C / +224.6°F for 296 days
- Nuclear Qualification
- IEEE Std 323, IEEE Std 344, RCC-E
- Nuclear Standards
- ASME Section III, RCC-M, IEC 61513
- Functional Safety
- Design conforms to IEC 61508
- Device Integration
- FDT1.2 DTM certification
Enquire about this product
Pricing, availability, lead times and technical support — direct from our engineers.
Related products






Level Measurement — talk to our engineers
Continuous and point level measurement for liquids and solids