LEVEL MEASUREMENT TECHNOLOGIES
Ultrasonic level transmitters: level from the echo of a sound pulse
An ultrasonic level transmitter sits above the liquid and measures the time a sound pulse takes to reach the surface and come back. It gives continuous level with no contact, and it is a common choice for water and wastewater — wells, sumps, open tanks and open channels. Our catalogue includes the Delta Mobrey DMSP900SH, a two-wire ultrasonic level transmitter for wet wells and sumps.
How an ultrasonic level transmitter works
A transducer above the surface sends a short pulse of sound, above the range of hearing, and then listens for its echo from the liquid. The time between the two, multiplied by the speed of sound and halved, is the distance to the surface; the distance taken from the height of the tank is the level.
Sound travels at about 343 m/s in air at 20 °C, and faster as the air warms — by roughly 0.17 % for every degree. That is why ultrasonic transmitters measure the air temperature and correct for it.
Just below the transducer there is a blind zone: an echo from that close would return while the transducer is still ringing from its own pulse, so the highest level must stay below it. The Delta Mobrey DMSP900SH measures up to 15 metres, is two-wire loop powered with HART, and is IP68 and intrinsically safe certified.
- The sound pulse leaving the transducer, and its echo returning from the surface
- The blind zone just below the transducer, which the level must not enter
- The electronics, which time the echo and correct for the temperature of the air
- The 4–20 mA signal with HART to the control system
Where an ultrasonic level transmitter fits — and where it does not
A strong choice for
- Wet wells, sumps and pumping stations
- Open tanks and reservoirs of water and wastewater
- Open channels and flumes, where the level gives the flow
- Corrosive or dirty liquids, measured without contact
- Places that may flood: the DMSP900SH is IP68
Think twice when
- Foam covers the surface: it absorbs the pulse and the echo is lost
- There is vapour, steam or a gas other than air, or strong temperature layers: they change the speed of sound
- The tank is closed under pressure or vacuum, or the process temperature is very high
- Dust, heavy turbulence or internals in the beam give weak or false echoes
How it compares with the other technologies
- Hydrostatic level transmitters−20…+100 °C
- Radar level−40…+200 °C
- Ultrasonic level (the technology of this article)−40…+80 °C
- Vibrating level switches−40…+120 °C
- Floats and displacers−60…+320 °C
- Conductive and HF level switches−30…+150 °C
- Rotating paddle−20…+80 °C
Typical process temperatures, not a model commitment; several technologies have versions for higher temperatures. We confirm the figures of each instrument for your application.
Installing an ultrasonic level transmitter
Mount the transducer above the highest level plus the blind zone, pointing straight down at the surface, with the beam clear of the walls, ladders, pipes and the inlet stream.
Then:
- Keep the transducer perpendicular to the surface: a tilted one sends its echo away.
- Shade it from direct sun, which heats the air below it unevenly.
- Avoid points where foam collects, such as close to inlets.
- For pump control, set the start and stop levels in the controller or the PLC, with enough distance between them.
Ultrasonic level transmitters by industry
Ultrasonic level transmitters in our catalogue
The ultrasonic level transmitters in our catalogue, each with its own page and technical data.
Ultrasonic level transmitters: frequently asked questions
Ask about an ultrasonic level transmitter
Tell us the liquid, the tank, well or channel and its depth, the conditions above the surface (foam, vapour, temperature), the mounting and the output you need — and our engineers will suggest the right transmitter, with price and delivery time.