Level measurement: level transmitters and level switches — how they work and which one to choose

Level is measured in every tank, silo, well and vessel of a plant — to know the contents, to control a pump or a valve, or to stop a tank from overflowing and a pump from running dry. Some instruments give the level continuously; others only switch at a point. This page covers seven technologies — hydrostatic transmitters, radar, ultrasonic, vibrating switches, floats and displacers, conductive and HF switches, and the rotating paddle — how each one works, where it fits and where it does not, when you need a continuous measurement and when a switch is enough, and how to choose.

Seven ways to measure level

For each one: the principle in a sketch, where it fits and where it does not, and how many instruments of that technology are in our catalogue.

Hydrostatic level transmitters

A pressure sensor at the bottom of the tank or well measures the pressure of the liquid column above it. With a known density, that pressure is the height of the liquid — about 98 mbar for every metre of water. Submersible probes hang on their cable, which carries a vent tube to the atmosphere as the reference; flanged versions mount near the bottom of the tank.

Where it fits
Water and wastewater, wells, sumps, open tanks and reservoirs — simple and robust, and not affected by foam, vapour or anything above the liquid.
Where it does not
Closed or pressurised tanks, where the gas pressure adds to the reading, and liquids whose density changes.

Radar level: non-contact and guided wave

The transmitter sends microwave signals towards the surface and measures the time until their echo returns: non-contact radar sends them through the air from an antenna, guided wave radar along a rod or cable that reaches into the medium. The distance to the surface, taken from the height of the tank, gives the level.

Where it fits
Liquids and bulk solids in tall tanks and silos, with vapour, high temperatures and pressures; guided wave radar also under foam and for the interface between two liquids.
Where it does not
Simple jobs where a switch or a hydrostatic probe is enough, and installations where the beam cannot get past internals near the antenna.
Not in our catalogue yet — ask us about availability. See how we supply them Read the article

Ultrasonic level transmitters

A sensor mounted above the surface sends short pulses of sound and times their echo from the liquid. The time and the speed of sound give the distance, and from it the level — with no contact. The speed of sound changes with the temperature of the air, so the transmitter corrects for it.

Where it fits
Water and wastewater: wells, sumps, open tanks and open channels — the Delta Mobrey DMSP900SH is made for wet wells and sumps.
Where it does not
Foam, vapour, dust, heavy turbulence, and closed tanks under pressure or vacuum, which weaken the echo or change the speed of sound.

Vibrating level switches

A fork or a rod is kept vibrating at its resonant frequency by its electronics. When liquid or powder covers it, the vibration changes — it is damped and its frequency drops — and after a short delay the switch changes its output.

Where it fits
Overfill and dry-run protection in liquids, and high and low level in silos of powders and granules — with no moving parts.
Where it does not
Continuous level, and media that leave hard, heavy build-up between the tines.

Floats and displacers

Both use buoyancy. A float rides on the surface and, at a set level, moves a magnet that switches a contact. A displacer is heavier than the liquid and hangs from a spring or a torque element: as the level rises, the liquid lifts it with a force equal to the weight of the liquid it displaces, and the transmitter turns that change into a level signal.

Where it fits
Float switches for simple level alarms in tanks; displacers for level and interface in separators, knock-out pots and condensate drums, at high temperature and pressure.
Where it does not
Dirty, sticky or crystallising liquids that clog moving parts, and — for displacers — liquids whose density changes.

Conductive and HF level switches

Two electronic point-level switches with no moving parts. A conductive switch passes a small current between its electrode and the tank wall, or a second electrode, as soon as a conductive liquid touches it. An HF switch creates a high-frequency field at its tip and detects how the medium around the tip changes it.

Where it fits
Simple high and low limits in conductive liquids (conductive), and compact, hygienic switches for liquids, viscous media and pastes in food and pharmaceutical processes (HF).
Where it does not
Continuous level; and — for conductive switches — oils, solvents and other liquids that do not conduct electricity.

Rotating paddle level switches

A small motor turns a paddle slowly inside the silo. When the bulk solid covers the paddle and stops it, the switch signals the level; when the material falls away, the paddle turns again. The same switch can mark a high or a low level.

Where it fits
High and low level in silos and hoppers of powders, granules and dense solids — the Delta Mobrey paddle switch covers a broad range of material densities.
Where it does not
Liquids, and continuous level — a paddle switch only tells you whether the material has reached it.
1 product in our catalogue Show in the product list

At a glance

The typical properties of the seven technologies in one table, and their typical process temperature in one chart.

Level measurement technologies compared: what they give, contact with the medium, media, typical process temperature, output and main limitation
TechnologyGivesContact with the mediumMediaTypical process temperatureOutputMain limitation
Hydrostatic level transmittersContinuous levelSensor in the liquid, at the bottomLiquids, including wastewater and sludge−20…+100 °C4–20 mA, HARTReads level correctly only at a known, steady density; in a closed tank the gas pressure must be subtracted
Radar levelContinuous levelNon-contact; guided wave: a probe in the mediumLiquids and bulk solids−40…+200 °C4–20 mA, HARTHigher cost; build-up on the antenna and obstacles in the tank need care when installing
Ultrasonic levelContinuous levelNon-contactLiquids, wells, sumps and open channels−40…+80 °C4–20 mA, HARTFoam, vapour, dust and turbulence weaken or scatter the echo; a blind zone just below the sensor
Vibrating level switchesPoint level (switch)Fork or rod in the mediumLiquids, powders and granules−40…+120 °CRelay or transistor (PNP/NPN)Point level only; heavy, hard build-up between the tines can hold the switch
Floats and displacersPoint level or continuousFloat or displacer in the liquidClean liquids and liquid–liquid interfaces−60…+320 °CContact (float switch); 4–20 mA, HART (displacer)Moving parts in the liquid; a displacer reads correctly only at a known density
Conductive and HF level switchesPoint level (switch)Probe in the mediumConductive liquids (conductive); liquids and pastes (HF)−30…+150 °CRelay or transistor (PNP/NPN)Point level only; a conductive switch needs a liquid that conducts electricity
Rotating paddle Point level (switch)Paddle in the bulk solidBulk solids, from light powders to dense solids−20…+80 °CContactPoint level in solids only; moving parts, and the paddle must suit the bulk density of the material

Typical process temperatures, not a model commitment; several technologies have versions for higher temperatures. We confirm the figures of each instrument for your application.

Typical process temperature by technology

Typical process temperature of each technology, in °C. Versions for higher temperatures exist for several of them.
  • Hydrostatic level transmitters−20…+100 °C
  • Radar level−40…+200 °C
  • Ultrasonic level−40…+80 °C
  • Vibrating level switches−40…+120 °C
  • Floats and displacers−60…+320 °C
  • Conductive and HF level switches−30…+150 °C
  • Rotating paddle−20…+80 °C

Application guide: which technology for which job

Each level technology exists to solve a particular problem. Start from yours — the medium, the vessel, whether you need the level or a limit — and see which technology we would suggest, which one to avoid, and why.

Application guide for level measurement: for each application, the technology we suggest and why, and the one to avoid and why
ApplicationWe suggestWhyAvoidWhy not
Foam, vapour or condensation, or a medium that must not be touchedMicrowaves pass through vapour and are hardly affected by the temperature or pressure of the gas above the liquid; non-contact radar touches nothing, and under heavy foam guided wave radar keeps its pulse on the probe.Foam absorbs the sound pulse, and vapour and temperature change the speed of sound — the echo is lost or the distance is wrong.
Powders, granules and bulk solids in silos and hoppersRadar gives the continuous level of solids; for high and low limits, a vibrating rod such as the Delta Mobrey VLS, a fork such as the DMS & DMT, or a rotating paddle switch.Both work only in liquids: a hydrostatic sensor weighs a liquid column, and a float or a displacer needs buoyancy.
Wells, sumps and wastewaterA submersible probe such as the Klay AquaCer or HydroCer, made for water, wastewater and sludge, or the Delta Mobrey DSGE for tanks, deep wells and piezometers; or, with no contact at all, an ultrasonic transmitter such as the DMSP900SH, made for wet wells and sumps. — Any probe in the liquid must cope with rags, grease and sludge: hang a submersible probe above the bottom sludge, and keep moving parts out of the flow.
Hygienic process: food, dairy, beverages, pharmaceuticalsA flush diaphragm on a hygienic connection, as on the Klay 8000-SAN; compact switches such as the KMW, with EHEDG-compliant connections; and tuning forks with smooth wetted parts (Ra below 1.5 μm) and hygienic connections, such as the Klay Vibraswitch.Moving parts, hinges and chambers leave crevices where product stays and cleaning cannot reach.
Overfill and dry-run protection: high and low alarmsA separate switch keeps protecting the tank or the pump even if the continuous measurement or the control system fails, and an electronic switch has no moving parts to stick. — Do not rely only on an alarm from the continuous level transmitter: one failure would then take away both the measurement and the protection.
Interface between two liquids: oil and water in separatorsA displacer such as the Mobrey MLT100 measures interfaces with a specific gravity difference as low as 0.1; guided wave radar sees both the surface and the interface along its probe.Sound reflects from the top surface only; an ultrasonic transmitter cannot see the interface below it.
A liquid whose density changes: mixtures, batches, temperature swingsThey measure the distance to the surface, so the density of the liquid does not enter the reading.The pressure of a liquid column and the buoyancy on a displacer both depend on density: a lighter liquid reads as a lower level.
Sticky, viscous or coating media: sludge, syrups, resins, pastesNon-contact radar does not touch the medium; for limits, HF switches such as the KMW are made for liquids and viscous media, with a longer tip for viscous media and adjustable sensitivity.A coating on a float or a displacer changes its weight and can stop it from moving.
A simple limit in a conductive liquid: water, wastewater and other water-based liquidsA conductive switch such as the Klay FLX is the simplest electronic switch: one probe, a relay or PNP output and adjustable sensitivity, with insertion lengths from 20 mm to 2 m. — Not for oils, solvents or other liquids that do not conduct electricity; there, use a vibrating or an HF switch.
High temperature or high pressureThe Mobrey MLT100 displacer works from −60 to +320 °C and from full vacuum to 200 bar; radar is hardly affected by the temperature or pressure of the gas above the liquid.The transducer has a limited temperature range, and the speed of sound changes with the temperature and the pressure of the gas.

Continuous measurement or a point-level switch?

A level transmitter gives the level at every moment, as a 4–20 mA signal or over a fieldbus: for inventory, for controlling a pump or a valve, for trends and alarms in the control system. A level switch only says whether the medium has reached a point — high, low, overfill, dry-run.

Most tanks need both. The transmitter runs the process; separate switches at the critical points protect the tank and the pumps on their own, so that one failure cannot take away both the measurement and the protection.

  • Continuous level: hydrostatic transmitters, radar, ultrasonic transmitters and displacers.
  • Point level: vibrating, float, conductive, HF and rotating paddle switches.
  • A switch is simpler to set up: it needs no range, only the point where it is mounted.
  • For overfill protection, use a separate switch, not only an alarm on the continuous measurement.

How to choose a level technology

The right technology follows from the application. These are the criteria we look at:

  1. The level or a limit

    A value for control and inventory needs a transmitter; an alarm, a pump start or overfill protection can be a switch.

  2. Liquid or solid

    Hydrostatic sensors, floats and displacers work only in liquids; radar, vibrating rods and rotating paddles also in powders and granules.

  3. The vessel

    Open or closed, under pressure or vacuum, its height, internals such as agitators and ladders, and the nozzles available for mounting.

  4. The medium

    Its density and whether it changes, its conductivity, foam, vapour, build-up and viscosity — and whether it may be touched at all.

  5. Temperature and pressure

    The process conditions decide the technology and the version — see the typical temperatures in the chart above.

  6. Environment and signal

    Hazardous areas, hygiene rules, marine use, and the output the control system expects: 4–20 mA with HART, a relay or a transistor output.

Level measurement: frequently asked questions

Need help choosing a level instrument?

Tell us about the medium, the vessel and the operating conditions, and our engineers will recommend the right technology and the specific instrument.