| Foam, vapour or condensation, or a medium that must not be touched | | Microwaves pass through vapour and are hardly affected by the temperature or pressure of the gas above the liquid; non-contact radar touches nothing, and under heavy foam guided wave radar keeps its pulse on the probe. | | Foam absorbs the sound pulse, and vapour and temperature change the speed of sound — the echo is lost or the distance is wrong. |
|---|
| Powders, granules and bulk solids in silos and hoppers | | Radar gives the continuous level of solids; for high and low limits, a vibrating rod such as the Delta Mobrey VLS, a fork such as the DMS & DMT, or a rotating paddle switch. | | Both work only in liquids: a hydrostatic sensor weighs a liquid column, and a float or a displacer needs buoyancy. |
|---|
| Wells, sumps and wastewater | | A submersible probe such as the Klay AquaCer or HydroCer, made for water, wastewater and sludge, or the Delta Mobrey DSGE for tanks, deep wells and piezometers; or, with no contact at all, an ultrasonic transmitter such as the DMSP900SH, made for wet wells and sumps. | — | Any probe in the liquid must cope with rags, grease and sludge: hang a submersible probe above the bottom sludge, and keep moving parts out of the flow. |
|---|
| Hygienic process: food, dairy, beverages, pharmaceuticals | | A flush diaphragm on a hygienic connection, as on the Klay 8000-SAN; compact switches such as the KMW, with EHEDG-compliant connections; and tuning forks with smooth wetted parts (Ra below 1.5 μm) and hygienic connections, such as the Klay Vibraswitch. | | Moving parts, hinges and chambers leave crevices where product stays and cleaning cannot reach. |
|---|
| Overfill and dry-run protection: high and low alarms | | A separate switch keeps protecting the tank or the pump even if the continuous measurement or the control system fails, and an electronic switch has no moving parts to stick. | — | Do not rely only on an alarm from the continuous level transmitter: one failure would then take away both the measurement and the protection. |
|---|
| Interface between two liquids: oil and water in separators | | A displacer such as the Mobrey MLT100 measures interfaces with a specific gravity difference as low as 0.1; guided wave radar sees both the surface and the interface along its probe. | | Sound reflects from the top surface only; an ultrasonic transmitter cannot see the interface below it. |
|---|
| A liquid whose density changes: mixtures, batches, temperature swings | | They measure the distance to the surface, so the density of the liquid does not enter the reading. | | The pressure of a liquid column and the buoyancy on a displacer both depend on density: a lighter liquid reads as a lower level. |
|---|
| Sticky, viscous or coating media: sludge, syrups, resins, pastes | | Non-contact radar does not touch the medium; for limits, HF switches such as the KMW are made for liquids and viscous media, with a longer tip for viscous media and adjustable sensitivity. | | A coating on a float or a displacer changes its weight and can stop it from moving. |
|---|
| A simple limit in a conductive liquid: water, wastewater and other water-based liquids | | A conductive switch such as the Klay FLX is the simplest electronic switch: one probe, a relay or PNP output and adjustable sensitivity, with insertion lengths from 20 mm to 2 m. | — | Not for oils, solvents or other liquids that do not conduct electricity; there, use a vibrating or an HF switch. |
|---|
| High temperature or high pressure | | The Mobrey MLT100 displacer works from −60 to +320 °C and from full vacuum to 200 bar; radar is hardly affected by the temperature or pressure of the gas above the liquid. | | The transducer has a limited temperature range, and the speed of sound changes with the temperature and the pressure of the gas. |
|---|