OPTIBAR DP 7060
Technology: Differential pressure transmitters
Differential pressure transmitter with integrated absolute pressure cell for flow, level, density and interface measurement, 30 mbar to 16 bar, ±0.065% accuracy.
The OPTIBAR DP 7060 measures differential pressure and, with the same device, the static line pressure, which it uses to limit the effect of line-pressure changes on the output and to provide a second process signal. It can be combined with KROHNE primary elements such as orifice plates or pitot tubes for flow, or fitted with diaphragm seals for hydrostatic level, interface and density measurements. Step response is below 125 ms and the turndown ratio reaches 100:1, with higher values on request. Output options include 4…20 mA/HART, Foundation Fieldbus and Profibus-PA, plus Bluetooth for commissioning through the OPTICHECK Pressure Mobile app.
Specifications
- Measuring Range (DP)
- 30 mbar…16bar / 0.44…232 psi
- Line Pressure
- up to 700 bar / 10,153 psi
- Reference Accuracy
- ±0.065%
- Step Response Time
- <125 ms
- Turndown Ratio
- up to 100:1, higher upon request
- Output Signals
- 2-wire, 4…20 mA/HART ®, FF, Profibus-PA, Bluetooth ®
- Hazardous Area Approvals
- Ex ia, Ex d, Ex t
- Functional Safety
- SIL 2/3
Enquire about this product
Pricing, availability, lead times and technical support — direct from our engineers.
Related products






Pressure Measurement — talk to our engineers
Pressure and differential-pressure process instruments