OPTIBAR OP 3100
Technology: Differential pressure
Orifice plate with carrier ring and corner taps for differential-pressure flow measurement of gases, steam and liquids, DN50…600, up to PN100.
The OPTIBAR OP 3100 is a separate-type orifice plate with a flat sealing face and corner taps, used as a differential-pressure flow element on aggressive and non-aggressive gases, steam and liquids. The plate is machined as one piece with the carrier ring for smaller diameters and screwed to it for larger ones. It is installed between standard pipe flanges on horizontal or vertical pipes, and a shut-off valve is available as an option. Sizing follows EN ISO 5167, ASME MFC-3M, AGA 3, ASME PTC 19.5 2004, GOST 8.586 and RD 50-411-83.
Specifications
- Size
- DN50…600
- Pressure Rating
- up to PN100
- Temperature
- up to +400°C / +752°F
- Material
- 1.4404 / 316L
- Sealing Face
- Flat
- Pressure Taps
- Corner taps
- Design
- Separate type, with carrier ring and optional shut-off valve
- Sizing Standards
- EN ISO 5167, ASME MFC-3M, AGA 3, ASME PTC 19.5 2004, GOST 8.586, RD 50-411-83
Enquire about this product
Pricing, availability, lead times and technical support — direct from our engineers.
Related products






Pressure Measurement — talk to our engineers
Pressure and differential-pressure process instruments